3KVA/50KV油浸式試驗(yàn)變壓器
技術(shù)參數(shù):
| 容量 | 高壓電壓(KV) | 高壓電流(mA) | 低壓輸入 | 變比 | 溫升℃ | |||
(KVA) | AC | DC | AC | DC | 電壓(V) | 電流(A) | 高/儀 | 30分鐘 | |
YD 1.5/50 | 1.5 | 50 | 70 | 30 | 15 | 200 | 7.5 | 500 | 10 |
YD 3/50 | 3 | 50 | 70 | 60 | 15 | 200 | 15 | 500 | 10 |
YD 5/50 | 5 | 50 | 70 | 100 | 15 | 200 | 25 | 500 | 10 |
YD 10/50 | 10 | 50 | 70 | 200 | 50 | 200 | 50 | 500 | 10 |
YD 20/50 | 20 | 50 | 70 | 400 | 100 | 400 | 50 | 500 | 10 |
YD 30/50 | 30 | 50 | 70 | 600 | 100 | 400 | 75 | 500 | 10 |
YD 40/50 | 40 | 50 | 70 | 800 | 105 | 400 | 100 | 500 | 10 |
YD 50/50 | 50 | 50 | 70 | 1000 | 100 | 400 | 125 | 500 | 10 |
YD 10/100 | 10 | 100 | 140 | 100 | 50 | 400 | 25 | 1000 | 10 |
YD 20/100 | 20 | 100 | 140 | 200 | 100 | 400 | 50 | 1000 | 10 |
YD 30/100 | 30 | 100 | 140 | 300 | 100 | 400 | 75 | 1000 | 10 |
YD 40/100 | 40 | 100 | 140 | 400 | 100 | 400 | 100 | 1000 | 10 |
YD 50/100 | 50 | 100 | 140 | 500 | 100 | 400 | 125 | 1000 | 10 |
YD 20/100 | 20 | 150 | 210 | 133 | 100 | 400 | 50 | 1500 | 10 |
YD 30/100 | 30 | 150 | 210 | 200 | 100 | 400 | 75 | 1500 | 10 |
YD 40/100 | 40 | 150 | 210 | 267 | 100 | 400 | 100 | 1500 | 10 |
YD 50/100 | 50 | 150 | 210 | 333 | 100 | 400 | 125 | 1500 | 10 |
YD 100/150 | 100 | 150 | 210 | 667 | 150 | 400 | 250 | 1500 | 10 |
3KVA/50KV油浸式試驗(yàn)變壓器
操作實(shí)驗(yàn)辦法:
1、 按上圖接線(xiàn),審查壓力表批示外部氣體壓力能否一般(≥0.3MPA)
2、 做交流耐壓時(shí)短路桿拔出孔J中,做直流走漏實(shí)驗(yàn),存入短路桿。
3、 限流電阻設(shè)置裝備擺設(shè):工頻耐壓每伏0.3~1歐:直流每伏5~10歐,正常試 驗(yàn)可不必。
4、 撤除被試品線(xiàn)引線(xiàn),套管及器身臟污肅清,多余時(shí)采納屏障措施。
5、 預(yù)備任務(wù)和保險(xiǎn)措施停當(dāng),空試一次設(shè)備。
6、 接上被試品,直流實(shí)驗(yàn)使用屏障線(xiàn),以排除雜散走漏。
7、 合上電源,掌握箱(柜)電源指示綠燈亮。
8、 按下起動(dòng)旋鈕,起動(dòng)批示燈亮。
9、 對(duì)于掌握箱,逆時(shí)針勻稱(chēng)加電,凝視電壓抒發(fā)到額外電壓值。
10、 延續(xù)規(guī)則耐壓時(shí)間并凝視電流表批示。
11、 耐壓時(shí)間到,凝視KV表,疾速勻稱(chēng)降零。
12、 做圖2試驗(yàn)后用放電棒經(jīng)電阻放電,而后直接接地放電。
13、 高壓全體能夠被充洪水位置逐個(gè)放電后,改觀或者撤除高壓引線(xiàn),及所有引線(xiàn)至此一次實(shí)驗(yàn)停止。